The virtual synchronous generator (VSG) introduces rotational inertia and damping through the droop control to take part in frequency regulation of the grid. By building the VSG model, the VSG controller, including both the frequency controller and the excitation controller, are analysed and designed. The analysis shows that the large phase difference Delta theta between the VSG voltage and the grid voltage at the grid-tied moment may produce large power and damage the VSG. The proposed pre-synchronization control minimizes the phase difference, which is implemented by replacing Delta theta with sin Delta theta to avoid any step change from Delta theta. The proposed method is able to simplify control, shorten pre-synchronization tracking time, and achieve high accuracy without a phase-lock loop. The built 12 kW VSG simulation and prototype verify the theoretical analysis, the proposed control and its associated design.