Indexed by:
Abstract:
Electromagnetic contactor is a kind of widely used electric product. When the voltage drops suddenly, the contactor will be open or closed frequently, and the circuit will be influenced seriously. Based on the research of CJ20-63A contactor dynamic equations were established during closing, closed and opening processes; the movement process of the moving contact and the bounce of the contacts were considered at the meantime. The experimental data shows the model is correct. Simulations were carried out with respect to different working states and various closing phase angles. Influences of the range, duration and occurrence time of voltage drop, and the variation of voltage phases on performance characteristics of contactors were analyzed; the result indicates that the influences of voltage sag on the contactor are related to the closing time directly in the closing process; and a critical time value should be considered after the contactor is closed. This research provides the basic for the further study on the intelligent AC contactor with anti-voltage sag. © 2011 Chinese Society for Electrical Engineering.
Keyword:
Reprint 's Address:
Email:
Version:
Source :
Proceedings of the Chinese Society of Electrical Engineering
ISSN: 0258-8013
CN: 11-2107/TM
Year: 2011
Issue: 24
Volume: 31
Page: 131-137
Cited Count:
SCOPUS Cited Count:
ESI Highly Cited Papers on the List: 0 Unfold All
WanFang Cited Count:
Chinese Cited Count:
30 Days PV: 1
Affiliated Colleges: