Abstract :
In order to improve the breaking speed of miniature circuit breakers, RecurDyn Flux and Altair Flux were used to build an electromagnetic trip simulation model coupled with multi-body dynamics and electromagnetism to simulate the electromagnetic trip process in the event of short-circuit fault. It analyzes the dynamic characteristic curves during the contact separation process to explore the factors affecting the breaking speed, and the actual electromagnetic trip process was photographed by high-speed camera to verify the simulation model. Based on the simulation model, the orthogonal experiment is designed for the three factors that affect the breaking speed, and the optimal combination of factors is obtained. The test results show that the design scheme can increase the breaking speed of mini circuit breaker by 24.17% compared with the original prototype. © Beijing Paike Culture Commu. Co., Ltd. 2025.
Keyword :
Digital elevation model Digital elevation model Electromagnetic transients Electromagnetic transients Integrated circuit design Integrated circuit design Reclosing circuit breakers Reclosing circuit breakers Timing circuits Timing circuits
Cite:
Copy from the list or Export to your reference management。
GB/T 7714 | Gao, Yan , Xu, Zhihong . Electromagnetic Trip Simulation and Orthogonal Experiment Design of Miniature Circuit Breaker [C] . 2025 : 121-130 . |
MLA | Gao, Yan 等. "Electromagnetic Trip Simulation and Orthogonal Experiment Design of Miniature Circuit Breaker" . (2025) : 121-130 . |
APA | Gao, Yan , Xu, Zhihong . Electromagnetic Trip Simulation and Orthogonal Experiment Design of Miniature Circuit Breaker . (2025) : 121-130 . |
Export to | NoteExpress RIS BibTex |
Version :
Abstract :
In addressing the issue of asynchronous closing during the closing process of multi-break electromagnetic switches, the mechanism of electromagnetic system inter-coupling was analyzed, and a coordinated closing control strategy for multi-break electromagnetic switches was proposed. By using a laser displacement sensor to collect contact displacement signals, the contact displacement signal of a single-pole switch is used as a reference displacement. Other switches follow this reference online, achieving synchronous control of contact displacements and thereby synchronizing the moment of closure. The GD32F103 microcontroller serves as the control core, combined with a dual closed-loop control strategy of displacement and current to set up the experimental platform. Experimental results show that the coordinated closing control strategy effectively enhances the synchronicity of the closing moment. © Beijing Paike Culture Commu. Co., Ltd. 2025.
Keyword :
Closed loop control systems Closed loop control systems Electric switches Electric switches Phase locked loops Phase locked loops
Cite:
Copy from the list or Export to your reference management。
GB/T 7714 | Chen, Qitao , Xu, Zhihong . The Research on Coordinated Closing Control Strategy for Multi-break Electromagnetic Switches [C] . 2025 : 187-195 . |
MLA | Chen, Qitao 等. "The Research on Coordinated Closing Control Strategy for Multi-break Electromagnetic Switches" . (2025) : 187-195 . |
APA | Chen, Qitao , Xu, Zhihong . The Research on Coordinated Closing Control Strategy for Multi-break Electromagnetic Switches . (2025) : 187-195 . |
Export to | NoteExpress RIS BibTex |
Version :
Abstract :
Addressing the issue of electrical fires caused by DC series arc fault in long-serving photovoltaic systems due to line aging and poor contact, this paper proposes a fault detection method that combines multi-feature fusion fault criteria with machine learning algorithms. Initially, an arc generator is designed and integrated into the photovoltaic system to produce DC arc fault waveforms, with arc data collected using sensors and oscilloscopes. Subsequently, arc features are extracted from various domains and feature selection is performed using the random forest algorithm to eliminate redundant features, forming feature criteria. Finally, arc fault detection is carried out using a support vector machine optimized by particle swarm optimization. Experimental results show that this method can accurately identify DC series arc fault in photovoltaic systems and has a certain degree of anti-interference capability. © Beijing Paike Culture Commu. Co., Ltd. 2025.
Keyword :
Adaptive boosting Adaptive boosting Decision trees Decision trees Feature Selection Feature Selection Particle swarm optimization (PSO) Particle swarm optimization (PSO) Random forests Random forests Support vector machines Support vector machines
Cite:
Copy from the list or Export to your reference management。
GB/T 7714 | Cao, Feng , Xu, Zhihong . PSO-SVM Based DC Series Arc Fault Detection Method in Photovoltaic Systems [C] . 2025 : 697-705 . |
MLA | Cao, Feng 等. "PSO-SVM Based DC Series Arc Fault Detection Method in Photovoltaic Systems" . (2025) : 697-705 . |
APA | Cao, Feng , Xu, Zhihong . PSO-SVM Based DC Series Arc Fault Detection Method in Photovoltaic Systems . (2025) : 697-705 . |
Export to | NoteExpress RIS BibTex |
Version :
Abstract :
During the operation of the electromagnetic switches, the flux linkage can replace the mechanical parameters to characterize the motion of the actuator. But the observation errors of the flux linkage will lead to a failure of the control strategy. To address this issue, a cascade control strategy based on flux linkage slope is proposed. The observed flux linkage is intercepted by a sliding window, the flux linkage slope is calculated, then the flux linkage slope is used to establish a cascade control strategy. This strategy consists of an outer loop of the flux linkage slope and an inner loop of the coil current. The theoretical deduction proves that the flux linkage slope can be compatible with the flux linkage observation error and reflect the change of the real flux linkage caused by the motion of the armature. The simulation results show that the proposed cascade control strategy has good compatibility with the flux linkage observation error while realizing the self-adjusting of coil current with the displacement of the armature. © Beijing Paike Culture Commu. Co., Ltd. 2025.
Keyword :
Actuators Actuators Cascade control systems Cascade control systems Electric switches Electric switches
Cite:
Copy from the list or Export to your reference management。
GB/T 7714 | Zhang, Changkun , Su, Peiming , Xu, Zhihong . A Cascade Control Strategy for Electromagnetic Switches Based on Flux Linkage Slope [C] . 2025 : 594-601 . |
MLA | Zhang, Changkun 等. "A Cascade Control Strategy for Electromagnetic Switches Based on Flux Linkage Slope" . (2025) : 594-601 . |
APA | Zhang, Changkun , Su, Peiming , Xu, Zhihong . A Cascade Control Strategy for Electromagnetic Switches Based on Flux Linkage Slope . (2025) : 594-601 . |
Export to | NoteExpress RIS BibTex |
Version :
Abstract :
Aiming at the problem of arc extinguishing of HVDC relay, this paper presents an optimal design of electromagnetic system based on orthogonal test. In order to improve the breaking speed of the contact, a three-dimensional finite element model of the relay electromagnetic system is established. The key parameters of the electromagnetic system performance are analyzed, the optimization variables are determined, and the simulation model is verified by dynamic characteristic experiment. On this basis, the orthogonal test method is used to optimize the electromagnetic system of relay. The results show that the optimal design can improve the breaking speed of the relay contact and lay a theoretical foundation for improving the life of the relay. © Beijing Paike Culture Commu. Co., Ltd. 2025.
Keyword :
Design of experiments Design of experiments HVDC power transmission HVDC power transmission
Cite:
Copy from the list or Export to your reference management。
GB/T 7714 | Zhou, Yuxing , Xu, Zhihong . Optimization Design of Electromagnetic System for HVDC Relays Based on Orthogonal Experiment [C] . 2025 : 738-746 . |
MLA | Zhou, Yuxing 等. "Optimization Design of Electromagnetic System for HVDC Relays Based on Orthogonal Experiment" . (2025) : 738-746 . |
APA | Zhou, Yuxing , Xu, Zhihong . Optimization Design of Electromagnetic System for HVDC Relays Based on Orthogonal Experiment . (2025) : 738-746 . |
Export to | NoteExpress RIS BibTex |
Version :
Abstract :
The suddenness and obscurity of arc faults significantly complicate the detection and prediction of resultant fires, posing a serious threat to power systems and public safety. Accurate prediction and timely identification of fires induced by arc faults are essential. This article proposes a novel approach for arc fault fire prediction by fusing electrical signals with fire images, instead of relying solely on electrical signal detection. A fire data collection system is developed based on an arc fault experimental setup that adheres to standard requirements. The system collects multimodal data, including diverse types of arc fault signals and fire images. By analyzing this data, the mechanisms through which arc faults initiate and influence fire evolution are elucidated. A specialized tool is developed to annotate key timestamps in multimodal data and construct a high-quality dataset for model development. To address the complex application scenarios of arc fault fires, the fire prediction multimodal Fusion Transformer (FireMultiFormer) model is proposed. The model integrates fault signals and fire images to improve the accuracy of arc fault fire predictions. It uses the patch time-series Transformer (PatchTST) and the Vision Transformer (ViT) to extract features from current and image sequences, respectively, and employs a Fusion Transformer to fuse these multimodal features. This approach leverages data complementarity to improve the understanding and discrimination of fire states caused by arc faults. Experimental results show that the FireMultiFormer model achieves high accuracy and stability across various datasets. Case studies validate the model's ability to recognize and learn different fire states effectively. Ablation studies elucidate the impacts of model configurations and sample parameters on performance. Compared to single-modal and alternative methods, the multimodal model significantly improves performance in fire prediction. Furthermore, the proposed model enhances the performance of conventional arc fault detection methods by integrating image data.
Keyword :
Accuracy Accuracy Arc fault Arc fault Circuit faults Circuit faults Data collection Data collection Data models Data models electrical fire electrical fire Feature extraction Feature extraction fire prediction fire prediction fire prediction multimodal Fusion Transformer (FireMultiFormer) fire prediction multimodal Fusion Transformer (FireMultiFormer) multimodal fusion multimodal fusion Predictive models Predictive models Sensors Sensors Standards Standards Temperature sensors Temperature sensors Transformer Transformer Visualization Visualization
Cite:
Copy from the list or Export to your reference management。
GB/T 7714 | Du, Liwei , Xu, Zhihong , Gao, Jianhong et al. FireMultiFormer: A Transformer-Based Multimodal Approach for Predicting Arc Fault Fires With Fire Images and Fault Signals [J]. | IEEE TRANSACTIONS ON INSTRUMENTATION AND MEASUREMENT , 2025 , 74 . |
MLA | Du, Liwei et al. "FireMultiFormer: A Transformer-Based Multimodal Approach for Predicting Arc Fault Fires With Fire Images and Fault Signals" . | IEEE TRANSACTIONS ON INSTRUMENTATION AND MEASUREMENT 74 (2025) . |
APA | Du, Liwei , Xu, Zhihong , Gao, Jianhong , Chen, Duanyu . FireMultiFormer: A Transformer-Based Multimodal Approach for Predicting Arc Fault Fires With Fire Images and Fault Signals . | IEEE TRANSACTIONS ON INSTRUMENTATION AND MEASUREMENT , 2025 , 74 . |
Export to | NoteExpress RIS BibTex |
Version :
Abstract :
Most of the existing fault arc circuit breaker is only for single circuit single load. Aiming at the problem of complex running load of low-voltage power lines, set up an experimental platform to collect the current signals of series fault arcs in main and branch lines under the conditions of single load operation and multi-load operation of typical household loads, to create a waveform database. Various time-frequency domain feature quantities are extracted, and a subset of the feature quantity data is constructed by random forest and input to a regularized limit learning machine (RELM) for fault arc detection, and the most appropriate input weights and implied layer thresholds of the RELM are optimally selected by a particle swarm optimization (PSO) to improve the accuracy of fault arc identification. The result shows that the PSO-RELM algorithm achieves an accuracy of 98.37% and can accurately identify fault arcs in multi-load situations. © Beijing Paike Culture Commu. Co., Ltd. 2024.
Keyword :
Electric circuit breakers Electric circuit breakers Frequency domain analysis Frequency domain analysis Machine learning Machine learning Particle swarm optimization (PSO) Particle swarm optimization (PSO) Swarm intelligence Swarm intelligence
Cite:
Copy from the list or Export to your reference management。
GB/T 7714 | Chen, Hongda , Xu, Zhihong . Multi-load Series Fault Arc Identification Based on PSO-RELM [C] . 2024 : 117-125 . |
MLA | Chen, Hongda et al. "Multi-load Series Fault Arc Identification Based on PSO-RELM" . (2024) : 117-125 . |
APA | Chen, Hongda , Xu, Zhihong . Multi-load Series Fault Arc Identification Based on PSO-RELM . (2024) : 117-125 . |
Export to | NoteExpress RIS BibTex |
Version :
Abstract :
The actuator drivers are rarely transplanted among different contactors because the self-tuning of excitation control parameters either takes a long time or is relevant to many contactor structural parameters. An adaptive actuator driver for ac contactors is proposed based on the coil impedance estimation and mathematical equations between the coil impedance and excitation control parameters. The coil impedance estimation and its error correction are established through the voltage balance equation when the contactor is in the open position. The coil inductance estimation is established through the zero-state response equation when the contactor is in the closed position. The mathematical equations are established based on the equivalence of the electromagnetic force under different excitation methods, the power consumption model, and the control system's transfer function. A geometric feature of the flux linkage waveform is established to identify whether a contactor is in the closed position and realize the self-transition of the driver's working state. Then, self-tuning regulators for the excitation control parameters are realized. This driver has a plug-and-play function for ac contactors and can reduce the contactor's power consumption. This driver may be prospectively reduced to a chip.
Keyword :
Actuator Actuator contactor contactor estimation estimation self-tuning regulator self-tuning regulator
Cite:
Copy from the list or Export to your reference management。
GB/T 7714 | Zhang, Changkun , Xu, Zhihong . An Adaptive Actuator Driver for AC Contactors [J]. | IEEE TRANSACTIONS ON INDUSTRIAL ELECTRONICS , 2024 , 71 (4) : 3904-3914 . |
MLA | Zhang, Changkun et al. "An Adaptive Actuator Driver for AC Contactors" . | IEEE TRANSACTIONS ON INDUSTRIAL ELECTRONICS 71 . 4 (2024) : 3904-3914 . |
APA | Zhang, Changkun , Xu, Zhihong . An Adaptive Actuator Driver for AC Contactors . | IEEE TRANSACTIONS ON INDUSTRIAL ELECTRONICS , 2024 , 71 (4) , 3904-3914 . |
Export to | NoteExpress RIS BibTex |
Version :
Abstract :
In order to solve the problem of low efficiency of traditional intelligent contactor performance test, this paper proposes a contactor dynamic characteristic test and analysis system based on NI CompactRIO, which is convenient for measuring the performance index of intelligent contactor. The system includes a Human-Machine-Interaction(HMI) interface, which can control the action of the contactor to be detected and collect signals in the host computer platform. According to the trend of the collected signal waveform, the performance indexes of the contactor, such as the closing/opening time, the closing/holding power, are calculated. The system also has the functions of cyclic switching test and automatic data storage, which greatly improves the automation level and efficiency of the test. It provides data support for the improvement and optimization of the control strategy of intelligent contactor. © Beijing Paike Culture Commu. Co., Ltd. 2024.
Keyword :
Computer control systems Computer control systems Digital storage Digital storage Efficiency Efficiency
Cite:
Copy from the list or Export to your reference management。
GB/T 7714 | Tian, Yaoming , Xu, Zhihong . A Testing System Design of Dynamic Characteristics of Contactor Based on CompactRIO [C] . 2024 : 823-830 . |
MLA | Tian, Yaoming et al. "A Testing System Design of Dynamic Characteristics of Contactor Based on CompactRIO" . (2024) : 823-830 . |
APA | Tian, Yaoming , Xu, Zhihong . A Testing System Design of Dynamic Characteristics of Contactor Based on CompactRIO . (2024) : 823-830 . |
Export to | NoteExpress RIS BibTex |
Version :
Abstract :
The arc extinguishing system is the main component of the micro circuit breaker, and the structural parameters such as the arc extinguishing grid, the size of the outlet hole, and the contact angle affect the breaking capacity of the micro circuit breaker. In this paper, an arc simulation model is built based on magnetohydrodynamics. On this basis, the transient process of short-circuit current is taken into account to improve the accuracy of the simulation model, and the validity of the model is verified by experiments. Based on the simulation model, the influence of arc extinguishing grid and outlet hole size on the arc extinguishing ability of micro circuit breaker is analyzed by arc shape and external characteristics. The results show that increasing the arc extinguishing grid will make it difficult for the arc to enter the grid, but at the same time, it can increase the arc voltage and promote the extinction of the arc. In terms of the outlet hole, the uneven distribution of the arc when the outlet hole size is 2 mm and 4 mm will cause the arc to blow out from the grid, and the phenomenon of the arc blowing out from the grid can be effectively avoided when the outlet hole size is 3 mm. © Beijing Paike Culture Commu. Co., Ltd. 2024.
Keyword :
Circuit simulation Circuit simulation Contact angle Contact angle Electric circuit breakers Electric circuit breakers Magnetohydrodynamics Magnetohydrodynamics Timing circuits Timing circuits
Cite:
Copy from the list or Export to your reference management。
GB/T 7714 | Li, Xiaodong , Liu, Xiangjun , Xu, Zhihong . Simulation and Research on Short Circuit Breaking Arc Characteristics of Micro Circuit Breaker [C] . 2024 : 32-40 . |
MLA | Li, Xiaodong et al. "Simulation and Research on Short Circuit Breaking Arc Characteristics of Micro Circuit Breaker" . (2024) : 32-40 . |
APA | Li, Xiaodong , Liu, Xiangjun , Xu, Zhihong . Simulation and Research on Short Circuit Breaking Arc Characteristics of Micro Circuit Breaker . (2024) : 32-40 . |
Export to | NoteExpress RIS BibTex |