Abstract:
In order to locate the line where single pole grounding or pole to pole short circuit fault has occurred in a DC distribution network quickly, a location scheme is proposed and it is on the based of the Cos-similarity of current integrals. The DC bus current was transformed with fast Fourier firstly, then energy entropy of the transform was calculated, and it was used as the fault detection criterion. The fault location algorithm was activated when the fault detection criterion was satisfied, and then integral calculation of the currents before and after the fault at both ends of all DC distribution line were carried out. Then the Cos-similarity of current integrals were calculated. Location of the fault line and selection of pole were according to the comparison of the calculation results.Simulation results show that the scheme can locate the faults quickly and accurately in both of single pole grounding and pole to pole short circuit, which lays a good foundation for subsequent fault processing. © 2022 Editorial Department of Electric Machines and Control. All rights reserved.