The "chimney rain" problem can effectively be solved by adding a secondary dehydration device inside the chimney with wet flue gas desulfurization (FGD) direct-discharged measures in coal fired power station. In order to analyze the changes of outlet moisture content and internal flow field, and to optimize the structure of device to match the dehydration capacity and working resistance, a computational fluid dynamics (CFD) method was adopted to simulate the internal flow field of the chimney. Results show that after installing a secondary dehydration device the outlet moisture ratio decreases from 111 mg/m3 to 52 mg/m3; the working resistence increases in an allowable range, from 195 Pa to 699 Pa, which is below 1200 Pa; the outlet velocity raises from 17.3 m/s to 17.6 m/s. The smoke spirals up along inwall, not along central zone; the optimum angle of the whirl board is 42 degrees. Through the comparative analysis of actual and simulation results, the effectivity of the device and the feasibility of optimum angle were verified, and the basic laws and characteristics curves of internal flow field were also obtained.