Under the incomplete phase operation of EHV transmission line with shunt reactor and neutral reactor after the extinguishment of transient fault arc, a complex circuit with shunt reactor, neutral reactor, distributed capacitance and distributed impedance is formed. In order to study its characteristics, a relative accurate transient circuit with lumped parameters is set up through simplification, for which the Laplacian equations are deduced to calculate its eigenvalues and obtain its operational features. Its correctness is verified by the comparison with ATP simulation results. According to the natural component frequency calculated by proposed method for the faulty phase voltage, its natural component and compulsive component are extracted and their ratio can be used as the criterion for arc extinguishment of faulty phase.
Keyword:
Reprint 's Address:
Email:
Source :
Electric Power Automation Equipment
ISSN: 1006-6047
Year: 2010
Issue: 2
Volume: 30
Page: 48-52