In order to realize the intelligent navigation and obstacle avoidance of unmanned aerial vehicles (UAV), the distribution characteristics of spatial electric field intensity are studied in the paper. A three-dimensional calculation model of AC 500 kV vertical crossing 220 kV transmission line was established to study the electric field intensity distribution in the paper by using the estimation method of three-dimensional electric field and the finite element analysis software (Ansys). The results show that the electric field intensity rises at first and then goes down with the change of the test point height in the case of keeping the horizontal distance. The higher voltage level line plays a leading role in the crossing area. In addition, the electric field intensity is obviously decreased along with the increase of the distance between the test point and the crossing area in the case of keeping the height of test point. In this paper, a small multi rotor UAV equipped with test equipment is used to measure the electric field in the crossing area. The result shows that the error value is within the allowable range, which proves the validity of the analytic results. The research of this paper provides reference value for the analysis of space electromagnetic field. © 2017, Harbin University of Science and Technology Publication. All right reserved.