Abstract:
Arcless intelligent DC contactor based on IGBT hybrid connection closed-loop control strategy is proposed to solve the problem of contact burning loss caused by breaking arc of mechanical switches. The arcless breaking of DC contactor is realized in the way of single tube IGBT hybrid connection, which avoids the defects of large volume and high cost of IGBT modules. Based on the corresponding buffer circuit, the static current balance closed-loop control strategy is adopted to solve the problem of voltage imbalance and current imbalance caused by IGBT hybrid connection, which realizes the high utilization rate of IGBT and guarantees the reliable arcless breaking and stability of system. On this basis, the relevant constraint equations of the buffer circuit parameters are obtained by theoretical analysis, which provides the theoretical basis for the circuit optimization and further reduces the cost and volume of the control module. Experimental results show that the proposed control scheme is simple and effective, and has good versatility. © 2019, Electric Power Automation Equipment Press. All right reserved.
Keyword:
Reprint 's Address:
Email:
Source :
Electric Power Automation Equipment
ISSN: 1006-6047
Year: 2019
Issue: 1
Volume: 39
Page: 46-52
Cited Count:
SCOPUS Cited Count: 3
ESI Highly Cited Papers on the List: 0 Unfold All
WanFang Cited Count:
Chinese Cited Count:
30 Days PV: 1
Affiliated Colleges: