Abstract:
Aiming at complex industrial processes, a method considering the influence of operation mode and equipment standby for evaluating the voltage sag tolerance characteristics of industrial processes is proposed, which takes the PIT(Parameter Immunity Time) as the voltage sag tolerance index. The connectivity of nodes under current operation mode is analyzed, and the impact range is analyzed with the occurrence point of voltage sag. Then the original process fault tree is established and corrected according to the judgment result of the disturbed equipment. The whole process PIT is calculated by using PIT of a single device to evaluate the whole process voltage sag tolerance characteristics. The production process of an actual TFT-LCD(Thin Film Transistor Liquid Crystal Display) is analyzed and the analytical results prove the correctness and feasibility of the proposed method. © 2019, Electric Power Automation Equipment Press. All right reserved.
Keyword:
Reprint 's Address:
Email:
Source :
Electric Power Automation Equipment
ISSN: 1006-6047
Year: 2019
Issue: 12
Volume: 39
Page: 205-211
Cited Count:
SCOPUS Cited Count: 10
ESI Highly Cited Papers on the List: 0 Unfold All
WanFang Cited Count:
Chinese Cited Count:
30 Days PV: 1