Abstract:
Aiming at the insufficiency of oil-paper insulation aging state evaluation by the dielectric response theory, a method for diagnosing the oil-paper insulation of transformer is proposed. The differential spectral curve of transformer recovery voltage is unfolded, and the relationship between sub-curve quantity and insulation aging state as well as the relationship between relaxation time constant ratio Kτ and insulation aging state are analyzed for the diagnosis of transformer oil-paper insulation aging state. The test data of multiple transformers are analyzed and conclusions are obtained: the time-domain sub-curve quantity of recovery voltage differential spectral curve changes according to the oil-paper insulation state, the more serious the oil-paper insulation aging state is, the bigger the sub-curve quantity is; and Kτ can be used to diagnose the relative aging state of insulation oil to insulation paper. © 2017, Electric Power Automation Equipment Press. All right reserved.