Indexed by:
Abstract:
The dielectric response function with relaxation factor was applied to the analysis of the time-domain dielectric spectrum of the recovery voltage, the spectrum of the time-differential dielectric line was decomposed, the sub-spectral lines containing different relaxation information were obtained, the transformer oil-paper insulation topological structure was determined, and relaxation parameters were found. Further, the relaxation parameters and self-insulation status of more than 30 different models of oil-paper insulation transformers were analyzed. The relationship between relaxation factors and deterioration of transformer insulating oil and aging of transformer paper was excavated, and new characteristic quantities-the average relaxation factor of insulating oil and insulating paper averages were proposed to evaluate insulation status of insulating oil and insulating paper in oil-paper transformers. Finally, the actual transformer test data was used for analysis and verification. The results prove that the two new feature quantities can effectively evaluate the insulation status of the insulating oil and insulating paper in the transformer. © 2019, Harbin University of Science and Technology Publication. All right reserved.
Keyword:
Reprint 's Address:
Email:
Source :
Electric Machines and Control
ISSN: 1007-449X
Year: 2019
Issue: 12
Volume: 23
Page: 108-115
Cited Count:
SCOPUS Cited Count: 4
ESI Highly Cited Papers on the List: 0 Unfold All
WanFang Cited Count:
Chinese Cited Count:
30 Days PV: 0